Warren-controls 313 Overflow Trap Manuel d'utilisateur Page 4

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 16
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 3
4
2600 Emrick Blvd • Bethlehem, PA 18020 • USA •800-922-0085 • www.warrencontrols.com
INSTALLATION – TYPE 313
OVERFLOW TRAP
• To determine which 313 Overow Trap you
have locate the part number on the factory
serial number label (See Information Present
on 313 Overow Trap section for location of
important information on overow traps).
Then see 313 Overow Trap Specications
section to determine the performance and
physical characteristics of the overow trap).
• The overow trap must be installed in
vertical pipe with its inlet up as shown on the
installation orientation label (See Information
Present on 313 Overow Trap section for
location of important information on overow
traps).
• Eliminate vibration in piping. 313 Overow
Traps are not suitable in installations where
vibration exists.
• Before installing, be sure the 313 Overow
Trap and piping are clean inside and free
of scale, chips, welding spatter, and foreign
material. Thoroughly blow out or ush pipe
lines.
• Donotobscurefactoryserialnumberlabelor
installation orientation label with paint.
• Pipeplugmustbeinstalledinoatchamber
during operation.
OPERATION – TYPE 313 OVERFLOW TRAP
• Deaerators,tankswithsteamblankets,producecondensateasthesteamcondenses.The313OverowTrap
traps and relieves this condensate through its internal pilot while keeping the steam blanket from escaping.
Overow can occur if the water entering the tank exceeds its capacity. The 313 Overow Trap relieves the
overow through its internal single seated main stage valve. Buoyancy of the overow trap’s internal oat ball
provides force to actuate the internal pilot operated single seated valve assembly to relieve condensate and
overow to drain. It is normal for condensate to intermittently ash to steam as it is relieved to the drain. Steam
from the steam blanket however should not be continuously exiting the overow trap to the drain.
MAINTENANCE – TYPE 313
OVERFLOW TRAP
• 313OverowTrapsforthemostpartaremain-
tenance free when sized and chosen properly
for the application. Maintain the uid pres-
sure, pressure drop, and temperature within
the limits of the overow trap (See Informa-
tion Present on 313 Overow Trap section for
location of important information on overow
trap and 313 Overow Trap Specications sec-
tion to determine the performance and physi-
cal characteristics of the overow trap).
• Theinletandoutletoftheoverowtrapmust
be kept unblocked. The internal pilot operat-
ed single seated valve assembly must be kept
free of debris, deposits, and dirt. The internal
pilot operated single seated valve assembly
must move freely. The oat ball must not be
come lled with water. The oat lever must
be straight. Factory set-up of the overow
trap is shown on drawing 03130611101.
• Thewaterlevelinsidetheoatchambermust
cover the windows in the valve body in order
for the main stage to open.
• PerformFloatBallLevelTestduringscheduled
maintenance periods. Float ball level must be
correct for water to be at correct level in the
oat chamber. A set-up xture may also be
fabricated as shown on drawing 03130614111
to test and set the oat ball level.
• Pipeplugmustbeinstalledinoatchamber
during operation.
Vue de la page 3